EV5-255 makes an ideal safety critical, galvanic isolator where coaxial cables join two or more buildings together that are
connected to different phases of the mains supply. This can cause a potential difference at the earth. Joining these buildings
together, may cause extremely high balancing currents to flow along the coaxial cable/s.
When used as an AC galvanic isolator, DO NOT bridge the earth wire of the trunk cable going to the next building across the
body of the galvanic isolator. Only earth the system and galvanic isolator in its local building. Earth the coaxial cables in each
building separately to the MET of that building.
The cable safety sleeves MUST BE fitted to the F connectors of the output cables to protect the user/installer of the installation.